ACCA Manual S Calculator: Equipment Selection

Step 2 of the ACCA J-S-T-D HVAC design workflow

Check whether your HVAC equipment meets ACCA Manual S sizing limits. Enter your Manual J loads and the OEM capacity at your design conditions to get a PASS or FAIL verdict plus target CFM. Covers 8 equipment types, including the 2023 Manual S updates for variable-capacity and cold-climate heat pumps.

Manual S Equipment Sizing Check

Manual J Load Results

From Step 1 (Manual J) or full Manual J software output.

Approx 73% of total for average climates. Use full Manual J for humid areas.

SHR reminder: Sensible + Latent must equal Total Cooling Load. In humid Gulf Coast or Mid-Atlantic climates, latent load can be 30-40% of total.

Sources: Single-speed limits: ACCA Manual S 2014 Table 1. Variable-capacity and cold-climate HP limits: ACCA Manual S 2023 3rd Edition (ANSI/ACCA 3 Manual S-2023). SHR temperature differentials: ACCA Manual S brochure. Cold-climate HP rule: Top 5 Changes to Manual S.

ACCA Manual S Sizing Limits - All Equipment Types

Sourced from ACCA Manual S 2014 Table 1 and the 2023 3rd Edition updates for variable-capacity and cold-climate heat pumps. Percentages are of the Manual J load - not nominal equipment rating.

Equipment TypeCool MinCool MaxHeat MinHeat MaxSource
Single-Speed AC + Furnace95%115%100%140%Manual S 2014 Table 1
Multi-Stage/Two-Speed AC + Furnace90%120%100%140%Manual S 2023 3rd Edition
Variable-Capacity AC + Furnace90%130%100%140%Manual S 2023 3rd Edition
Heat Pump - Cooling Dominant95%115%100%Max capacityManual S 2014 Table 1
Heat Pump - Heating Dominant95%125%100%Max capacityManual S 2014 Table 1
Variable-Capacity Heat Pump90%130%100%Max capacityManual S 2023 3rd Edition
Cold-Climate Heat Pump (ccASHP)95%CL + 15k BTU max100%Max capacityManual S 2023 3rd Edition
Package AC Unit95%115%100%140%Manual S 2014 Table 1

Worked example: sizing a split system with the Manual S calculator

A single-story home in a mixed-humid climate returns these Manual J loads: total cooling 30,000 BTU/hr, sensible 22,500 BTU/hr, latent 7,500 BTU/hr, and heating 42,000 BTU/hr. The contractor selects a single-speed AC plus gas furnace and pulls the OEM expanded performance data at the local design conditions: 32,000 BTU/hr total cooling, 24,000 BTU/hr sensible, and 52,000 BTU/hr furnace output.

Enter those values and the Manual S calculator returns:

  • Sensible heat ratio: 75% (22,500 / 30,000).
  • Cooling check: 32,000 / 30,000 = 107% of load - PASS (limit 95-115%).
  • Heating check: 52,000 / 42,000 = 124% of load - PASS (limit 100-140%).
  • Target airflow: 974 CFM (about 390 CFM per ton), the number you carry into Manual T and Manual D.
  • Latent capacity: 32,000 - 24,000 = 8,000 BTU/hr, which clears the 7,500 BTU/hr latent load - OK.

Every result above reproduces exactly on the calculator at the top of this page - plug the same numbers in and confirm.