Manual D HVAC Duct Sizing Calculator
Step 4 of the ACCA J-S-T-D HVAC design workflow
A free HVAC duct sizing calculator built on the ACCA Manual D friction-rate method. Calculate friction rate, verify available static pressure, and size every duct run for sheet metal or flex duct, with verified upsizing rules.
Manual D Duct Design
Equipment Blower Data
Typical residential: 0.50-0.80 IWC. ECM blowers often rated to 0.70 IWC.
Used for CFM/ton ratio verification
Flex duct upsized 1 size (CFM < 800) or 2 sizes (> 800) vs metal.
Sources: ACCA Manual D duct sizing table at FR 0.10 IWC/100ft max 900 FPM. Flex duct upsizing rule (+1 size < 800 CFM, +2 sizes > 800 CFM). Friction rate wedge 0.06-0.18 IWC: ACCA Manual D.
Round Duct Size by CFM - ACCA Manual D Table
Sized at friction rate 0.10 IWC/100ft, maximum velocity 900 FPM for supply ducts. Flex duct rule: ACCA-based Residential Duct Sizing Guide.
| Airflow (CFM) | Sheet Metal | Flex Duct | Typical Application |
|---|---|---|---|
| 50 CFM | 5" | 5" | Bathrooms, powder rooms |
| 100 CFM | 6" | 6" | Small bedrooms |
| 150-200 CFM | 7-8" | 7-8" | Standard bedrooms |
| 250 CFM | 8" | 10" | Medium bedrooms (flex upsized 1 size) |
| 300-350 CFM | 9-10" | 10" | Large bedrooms, dining rooms |
| 400-500 CFM | 10-11" | 10-12" | Large rooms, open-plan spaces |
| 600-700 CFM | 12" | 14" | Main trunk branches |
| 800-950 CFM | 13-14" | 16" | Main supply trunk (flex upsized 2 sizes) |
| 1,000-1,200 CFM | 15-16" | 17-18" | 2.5-3 ton main supply trunk |
| 1,400-1,600 CFM | 17" | 19-20" | 3.5-4 ton main supply trunk |
| 1,800-2,000 CFM | 18" | 20-22" | 4-5 ton main supply trunk |
Flex duct note: Flex has a higher pressure drop and may require the size shown be increased by 1 round size for up to 800 CFM and 2 round sizes above 800 CFM. Fully extend and support flex duct at max 4-foot intervals.
Worked example: sizing a 1,200 CFM system
Say a 3.5-ton Manual J came back at 42,000 BTU/hr and 1,200 design CFM on an ECM blower rated to 0.70 IWC external static pressure. Enter those in step 1, keep the default component losses in step 2 (0.23 coil + 0.18 filter + 0.03 supply register + 0.03 return grille = 0.47 IWC), and the default layout in step 3 (60 + 40 supply, 50 + 30 return = 180 ft total effective length). Add three room loads in step 4: Master Bedroom 3,200, Living Room 5,800, Kitchen 4,200 BTU/hr.
- Available static pressure: 0.70 − 0.47 = 0.23 IWC
- Friction rate: (0.23 × 100) / 180 = 0.128 IWC/100ft, inside the 0.06–0.18 Manual D wedge
- CFM/ton: 1,200 ÷ (42,000 / 12,000) = 343, flagged just under the 350 low-airflow threshold
- Living Room: 43.9% of load → 527 CFM → 12" sheet metal or 13" flex at 572 FPM
- Master Bedroom: 24.2% → 291 CFM → 10" metal or 11" flex; Kitchen: 31.8% → 382 CFM → 10" metal or 11" flex
The friction rate lands in the wedge, so the design is valid. Run the same numbers in the calculator above and you will get these exact figures.