Manual D HVAC Duct Sizing Calculator

Step 4 of the ACCA J-S-T-D HVAC design workflow

A free HVAC duct sizing calculator built on the ACCA Manual D friction-rate method. Calculate friction rate, verify available static pressure, and size every duct run for sheet metal or flex duct, with verified upsizing rules.

Manual D Duct Design

Equipment Blower Data

Typical residential: 0.50-0.80 IWC. ECM blowers often rated to 0.70 IWC.

Used for CFM/ton ratio verification

Flex duct upsized 1 size (CFM < 800) or 2 sizes (> 800) vs metal.

Sources: ACCA Manual D duct sizing table at FR 0.10 IWC/100ft max 900 FPM. Flex duct upsizing rule (+1 size < 800 CFM, +2 sizes > 800 CFM). Friction rate wedge 0.06-0.18 IWC: ACCA Manual D.

Round Duct Size by CFM - ACCA Manual D Table

Sized at friction rate 0.10 IWC/100ft, maximum velocity 900 FPM for supply ducts. Flex duct rule: ACCA-based Residential Duct Sizing Guide.

Airflow (CFM)Sheet MetalFlex DuctTypical Application
50 CFM5"5"Bathrooms, powder rooms
100 CFM6"6"Small bedrooms
150-200 CFM7-8"7-8"Standard bedrooms
250 CFM8"10"Medium bedrooms (flex upsized 1 size)
300-350 CFM9-10"10"Large bedrooms, dining rooms
400-500 CFM10-11"10-12"Large rooms, open-plan spaces
600-700 CFM12"14"Main trunk branches
800-950 CFM13-14"16"Main supply trunk (flex upsized 2 sizes)
1,000-1,200 CFM15-16"17-18"2.5-3 ton main supply trunk
1,400-1,600 CFM17"19-20"3.5-4 ton main supply trunk
1,800-2,000 CFM18"20-22"4-5 ton main supply trunk

Flex duct note: Flex has a higher pressure drop and may require the size shown be increased by 1 round size for up to 800 CFM and 2 round sizes above 800 CFM. Fully extend and support flex duct at max 4-foot intervals.

Worked example: sizing a 1,200 CFM system

Say a 3.5-ton Manual J came back at 42,000 BTU/hr and 1,200 design CFM on an ECM blower rated to 0.70 IWC external static pressure. Enter those in step 1, keep the default component losses in step 2 (0.23 coil + 0.18 filter + 0.03 supply register + 0.03 return grille = 0.47 IWC), and the default layout in step 3 (60 + 40 supply, 50 + 30 return = 180 ft total effective length). Add three room loads in step 4: Master Bedroom 3,200, Living Room 5,800, Kitchen 4,200 BTU/hr.

  • Available static pressure: 0.70 − 0.47 = 0.23 IWC
  • Friction rate: (0.23 × 100) / 180 = 0.128 IWC/100ft, inside the 0.06–0.18 Manual D wedge
  • CFM/ton: 1,200 ÷ (42,000 / 12,000) = 343, flagged just under the 350 low-airflow threshold
  • Living Room: 43.9% of load → 527 CFM → 12" sheet metal or 13" flex at 572 FPM
  • Master Bedroom: 24.2% → 291 CFM → 10" metal or 11" flex; Kitchen: 31.8% → 382 CFM → 10" metal or 11" flex

The friction rate lands in the wedge, so the design is valid. Run the same numbers in the calculator above and you will get these exact figures.