Manual T Calculator: HVAC Register & Grille Sizing
Step 3 of the ACCA J-S-T-D HVAC design workflow
Size supply registers and return grilles room by room using ACCA Manual T methodology. This HVAC Manual T tool checks face velocity, throw distance, and return air grille size against verified ACCA and Hart & Cooley limits.
Manual T Register and Grille Sizing
System Airflow Data
Used for CFM/ton ratio check
Cooling: 55°F typical. Heating: 100-130°F. Affects throw.
Sources: Face velocity limits: Hart and Cooley Engineering Data. Return grille formula: ACCA Manual T via GreenBuildingAdvisor and aircondlounge.com. Cooling throw factor 0.75: ACCA Manual T and cedengineering.com M03-044.
Standard Register Sizes at 70% Net Free Area
Face Velocity = CFM / (Width × Height × 0.70 / 144). Source: Hart and Cooley Engineering Data and industry standard register sizing methodology.
| Register Size | Face (sq in) | Net Free (sq in / sq ft) | CFM @ 500 FPM | CFM @ 700 FPM | Typical Use |
|---|---|---|---|---|---|
| 4" x 10" | 40 | 28 (0.19) | 97 | 136 | Small bedrooms, bathrooms |
| 6" x 10" | 60 | 42 (0.29) | 146 | 204 | Standard bedrooms |
| 6" x 12" | 72 | 50 (0.35) | 175 | 245 | Medium bedrooms, office |
| 8" x 10" | 80 | 56 (0.39) | 194 | 272 | Larger bedrooms |
| 10" x 10" | 100 | 70 (0.49) | 243 | 340 | Large bedrooms, dining room |
| 10" x 12" | 120 | 84 (0.58) | 291 | 408 | Living room, open spaces |
| 12" x 12" | 144 | 101 (0.70) | 350 | 490 | Large living rooms, great rooms |
| 14" x 8" | 112 | 78 (0.54) | 272 | 381 | Open plan spaces, trunk registers |
Related free tools